PZH R2*M is a surge arrester according to EN 61643-11 ed.2 (IEC 61643-11:2011) consisting of high energy varistors in combination with gas discharge tube, which ensures zero leakage current in the PE conductor. Its parameters enable its use in complex circumstances. The device is to be installed on the interface of LPZ 1 – LPZ 2 and higher zones according to standard EN 62305 ed.2 (IEC 62305:2010), i.e. into subsidiary switchboards and control boxes. S indication specifies a version with remote monitoring. M indication specifies a type of construction with removable module.
| System configuration TN-C-S | True |
| Nominal discharge surge current (8/20) | 20 kA |
| System configuration DC | False |
| Nominal voltage AC | 230 V |
| System configuration IT | False |
| Max. continuous voltage AC | 275 V |
| System configuration TN-C | False |
| System configuration TN-S | True |
| System configuration TT | True |
| Number of conductors (without earthing) | 2 |
| Voltage protection level | 1,25 kV |
| Voltage protection level L-N | 1,25 kV |
| Max. discharge surge current (8/20) | 50 kA |
| Voltage protection level N-PE | 1,4 kV |
There are currenty no files for your language.